Wird geladen...
Wird geladen...
Onset temperature, gas quantity, heat release: cell chemistry defines the hazard profile of a battery energy storage system — and thus whether the compartmentation must be designed primarily against heat or against gas.
From a fire protection standpoint, "battery storage" is not a homogeneous category. Whether a cell is based on lithium iron phosphate (LFP), nickel manganese cobalt (NMC) or sodium-ion chemistry fundamentally changes three parameters: the temperature at which thermal runaway sets in, the heat released in the process, and the quantity and composition of the vent gases. For barrier design this leads to a simple but often overlooked consequence: the dominant protection objective depends on the chemistry — sometimes thermal compartmentation takes priority, sometimes gas and explosion management.
The structural difference lies in the cathode material: NMC cells use a layered oxide that can release oxygen at high temperatures and feed the fire from within. The olivine structure of LFP, by contrast, binds the oxygen firmly — the reaction is considerably less violent, but by no means harmless.
By comparison, NMC cells enter thermal runaway earlier — typical onset temperatures, depending on cell type and measurement method, lie roughly in the range of 170 to 210 °C — and then react most violently. Comparative studies record the highest vent gas temperatures for NMC (around 1,050 °C in a recent study, against roughly 446 °C for LFP) and the largest gas quantity per ampere-hour. On top of that come frequent flame ejection, sparking and cell particles that act as ignition sources for adjacent areas.
For compartmentation this means: with NMC systems the thermal load dominates. Partition walls and linings must absorb very high temperatures and heat fluxes for short periods without allowing the temperature on the rear face to rise critically. High-temperature-resistant insulation materials with proven behaviour above 1,000 °C, mechanically stable facing layers against particle impact and propagation-inhibiting interlayers between modules are the key building blocks here.
LFP is rightly regarded as thermally more stable: a higher onset temperature, lower heat release, and self-sustaining fires are rarer. But this frequently leads to the false conclusion that LFP is uncritical in fire protection terms. Comparative measurements do show the smallest gas quantity per unit of capacity (around 0.02 mol/Ah in a recent study, against roughly 0.07 mol/Ah for NMC), but with the highest hydrogen share in the vent gas — around 41 per cent in the same investigation.
The LFP Paradox
Precisely because LFP vent gases often do not ignite immediately, they can accumulate unnoticed in the enclosure or room. If the hydrogen-rich cloud later meets an ignition source, a delayed deflagration threatens — a scenario that has been the principal cause of loss in several real incidents. With LFP, the protection objective therefore shifts from the pure fire barrier towards gas detection, ventilation and explosion venting to NFPA 68/69.
For the lining this means: it must not only contain heat but also support gas management — keep defined vent paths clear, avoid blocking explosion relief areas, and itself create no ignition sources or voids where gas can accumulate.
In initial comparative studies, sodium-ion cells show a favourable safety profile: onset temperatures roughly at LFP level (in the order of 220 to 260 °C) and considerably lower maximum vent gas temperatures than either lithium chemistry. The option of discharging cells to zero volts for transport and storage also reduces risks over the life cycle.
Nevertheless, sodium-ion cells also release combustible gases in a fault condition — with relevant proportions of hydrogen, carbon monoxide and electrolyte vapours. The data base is still thin, too: only a few independent studies exist and hardly any large-scale fire tests at system level. For design work this means: do not lower the requirements for compartmentation, gas venting and explosion relief across the board, but demand project-specific test data (for instance to UL 9540A) and base the design on it.
Anton Brem
Managing Director
Refractory construction, high-temperature insulation and fire protection in industrial plants
Everything you need to know about LFP, NMC and Sodium-Ion from a Fire Protection Perspective: What Cell Chemistry Means for the Barrier
Your question not listed?
Request a personal consultationWhether complete relining, repair or emergency — free initial consultation and a fast response.